Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
5 - 4 Installation and Testing Issue 13 December 2000
Installing Shelves and Batteries, continued
Multiple-Shelf
Plants
A multiple-shelf CPS plant is composed of:
an initial shelf, which provides for:
rectifiers
converters or ringing generators
a control unit
an LVD contactor (see Note below)
associated control and temperature compensation circuits
output bus bars, which are used to interconnect the shelves and
connect the batteries
one or two supplemental shelves, each of which provides for:
rectifiers
converters or ringing generators
output bus bars, which provide terminations for the plant’s
primary output
Note: The initial shelf must be installed as the top or bottom shelf in a
three-shelf system.
Note
The LVD disconnect/reconnect feature is not available for
multiple shelf plants with N + 1 loads greater than 150
amperes.