9057 Event Log Database Item Size RdOnly Management information: The size of every item.
9058-9059 Event Log Database Size RdOnly
Management information: The size of the database, the size
includes management information.
(Total_Item*Item_Size+management_info_size).
9060-9075
Numeric Input Object and ASCII
Input Object data
RdOnly
These 16 registers represent the latest entries, when the OIT
operator enters a numeric or ASCII value into one of these
objects. Register 9075 is the latest entry.
9076-9079 Reserved for future use
9080-9085 Project name RdOnly
Twelve bytes are used to store the project name. Use the ASCII
Data Object to display on OIT.
9086-9087 Project size RdOnly
Four bytes are used to store the size of the current project (in
bytes). Use the Numeric Data Object (Decimal Display) to
display on OIT
9088-9089 Project size (Kbytes) RdOnly
Four bytes are used to store the size of the current project (in
bytes). Use the Numeric Data Object (Decimal Display) to
display on OIT.
9090-9091 Compiler Version ID RdOnly
Four bytes are used to store the compiler version of the current
project. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9092 Project Compiled Date: Year RdOnly
This register contains the year date when the project was last
compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9093 Project Compiled Date: Month RdOnly
This register contains the month date when the project was last
compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9094 Project Compiled Date: Day RdOnly
This register contains the day of month date when the project was
last compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9095-9099 Reserved for future use
9100 Indirect Window Object; window # RdOnly
This register stores the window number requested using the
Indirect Window Object
9101 Indirect Window Object; Offset R/W
This register can be used to store an offset that is added to
LW9100 when using the Indirect Window Object
9102-9129 Reserved for future use.
9130 Change language R/W V 2.5.0 -- This register changes the language set (Values:0-3)
9135 Battery Voltage (BIN) RdOnly
V 2.6.0 - Li-Battery Measurement (If value = 1175 = 3.02V) (If
value <1070 or 2.75V, then replace the battery)
Create a Numeric Display for LW:9135, set "Input high=1175"
and set "engineering high = 302" Then display should show
proper voltage.
9136 CF Recipe Transfer RdOnly
0:inactive
1:Transfer in process
2:Transfer complete
3:Transfer failed
9137-9999 Reserved for future use
Re served Rec ipe Word (RW) Ta ble
Address Function Access Description
60000
Real Time Clock (RTC);
Seconds
R/W
This register is used to store the seconds count for the optional
RTC; BCD code, valid values 0-59
60001
Real Time Clock (RTC);
Minutes
R/W
This register is used to store the minutes count for the optional
RTC; BCD code, valid values 0-59
60002
Real Time Clock (RTC);
Hour
R/W
This register is used to store the hour count for the optional RTC;
BCD code, valid values 0-23
60003
Real Time Clock (RTC);
Day Of Month
R/W
This register is used to store the day of the month for the optional
RTC; BCD code, valid values 0-31
1010-1001a, Rev 02
168 Sil ver Se ries In stal la tion & Op er a tion Man ual