P630 (G) LCD TOTAL FACTOR
Use this feature if the LCD Total increments/decrements by too large
(or small) an amount.
Enter the factor (powers of 10 only) by which actual volume is divided,
prior to LCD Total display.
e.g. for an LCD Total display in 1000’s of volume units, enter 3.
values: -3 = .001 3 = 1000
-2 = .01 4 = 10,000
-1 = .1 5 = 100,000
0 = 1 (preset) 6 = 1,000,000
1 = 10 7 = 10,000,000
2 = 100
P633 (G) LCD TOTAL DECIMAL
Enter the maximum number of decimal places to be displayed.
In the RUN mode, the number of decimal places displayed is not automatically
adjusted. When the LCD Total value is so large as to exceed display
capabilities, the total "rolls over" to "0" and continues incrementing.
values: 0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P640 (G) REMOTE TOTAL FACTOR
Use this feature if the remote totalizer (device connected to the relay set for
"totalizer operation" Relay Function, P111 = 40), updates too slowly or rapidly.
Enter the factor (powers of 10 only) by which actual volume is divided, prior
to Remote Totalizer count increment.
e.g. for a Remote Totalizer update by 1000’s of volume units, enter 3.
values: -3 = .001 3 = 1000
-2 = .01 4 = 10,000
-1 = .1 5 = 100,000
0 = 1 (preset) 6 = 1,000,000
1 = 10 7 = 10,000,000
2 = 100
PL-507 120