MEASUREMENT RESPONSE
The HYDRO+ Measurement Response (P003) to material level changes is designed
to exceed even the most demanding installation requirements.
The Measurement Response setting automatically presets various parameters
affecting the HYDRO+ response to material level changes as follows:
Parameter Values Dependent on Measurement Response (P003)
(units) 1(slow) 2(medium) 3(fast)
P070 Failsafe Timer (min) 100 10 1
P700 Max Fill Rate (m/min) 0.1 1 10
P701 Max Empty Rate (m/min) 0.1 1 10
P702 Filling Indicator (m/min) 0.01 0.1 1
P703 Emptying Indicator (m/min) 0.01 0.1 1
P704 Rate Filter (option) 4 2 2
P710 Fuzz Filter (% of Span) 100 50 10
P713 Echo Lock Window (per P701 / P702 and time since last valid measurement).
P727 Scan Delay (s) 5 5 3
P841 Long Shot Number 10 5 2
If any of these parameters are independently altered, a Measurement Response
parameter alteration automatically resets the independently altered value.
Slower Measurement Response provides greater measurement
reliability. Faster independently set Max Fill/Empty Rates may be
impeded by Echo Lock, Scan Delay and Shot Delay values.
PL-507 154