mA OUTPUT PARAMETERS (P200 to P203, P210 to P215, P219)
If mA output alteration is required, alter the following parameters.
When a mA Output Parameter is accessed, the Point Type symbol changes to "mA".
P200 mA RANGE
Use this feature to alter the mA output range.
If option 1 or 2 is selected, the mA output is directly proportional to the mA
Function. (If the Reading is 100% (or equivalent Units) the mA output is 20 mA).
If option 3 or 4 is selected, the mA output is inversely proportional to the mA
Function. (If the Reading is 0% (or equivalent Units) the mA output is 20 mA).
value: 0 = off
1 = 0 to 20 mA
2 = 4 to 20 mA (preset)
3 = 20 to 0 mA
4 = 20 to 4 mA
P201 mA FUNCTION
Use this feature to alter the mA output/measurement relationship.
This value is automatically altered when Operation (P001) is altered.
mA Function when Operation is...
level "level", "differential", or "average"
space "space"
distance "distance"
volume "level" or "space" (see conditions
*
)
flow "OCM"
*
altered when a Tank Shape (P050) is programmed if the mA Allocation
has not been altered.
values: 0 = off
1 = level
2 = space
3 = distance
4 = volume
5 = flow
6 = head
7 = volume rate
PARAMETERS
PL-507 89