P202 mA ALLOCATION
Use this feature to alter the mA output/Point Number allocation. As preset,
the mA output pertains to Point Number 1.
This value may only be altered if Operation is set for
DPD
(Differential Level,
P001 = 4) or
DPA
(Average Level, P001 = 5).
To have the mA output proportional to the differential or average level,
allocate the mA output to Point Number 3.
Enter the Point Number the mA output is to be based upon.
values: 1 = Point 1
2 = Point 2
3 = Point 3
P203 (V) mA VALUE / TRANSDUCER
View the current mA output value for the Point Number displayed.
The value displayed does not include any adjustment made using the
4 or 20 mA Trim features (P214 / P215).
This is the value displayed as an Auxiliary Reading when is pressed
in the RUN mode.
values: 0.000 to 22.00
PL-507 90