INDEPENDENT mA SETPOINTS (P210 and P211)
Use these features to reference the minimum and/or maximum mA output
to any point in the measurement range.
If mA Function (P201) is set for "level", "space", or "distance", enter the
material level in Units (P004) or percent of Span (P007) as referenced
to Empty (P006).
If mA Function is set for "volume", enter the volume in Max Volume (P051)
units or as a percent of Max Volume.
If mA Function is set for "flow", enter the flowrate in OCM Max Flow (P604)
units or as a percent of OCM Max Flow.
If mA function is set for "head", enter the head in level units (P004) or
percent of Max Head (P603).
If mA function is set for "volume rate", enter the volume rate in volume / min.
Ensure the % symbol is displayed before attempting to enter a % value,
(see Keypad).
These features are preset dependent upon mA Range (P200) and mA
Function (P201).
P210 0/4 mA SETPOINT
Enter the value (in applicable units or %) to correspond to 0 or 4 mA.
values: -999 to 9999
P211 20 mA SETPOINT
Enter the value (in applicable units or %) to correspond to 20 mA.
values: -999 to 9999
PROGRAMMING
PARAMETERS
PL-507 91