INDEPENDENT mA LIMITS (P212 and P213)
Use these features to adjust the minimum and/or maximum mA
output value limits.
Typically, the value entered is to suit the minimum and/or maximum input limit
requirements of the device connected to the HYDRO+ mA output terminals.
P212 mA MIN LIMIT
Enter the minimum mA output value (in mA) to be produced.
This feature is preset to 0.0 or 3.8 mA, (per mA Function, P200).
values: 0.000 to 22.00
P213 mA MAX LIMIT
Enter the maximum mA output value (in mA) to be produced.
This feature is preset to 20.2 mA.
values: 0.000 to 22.00
INDEPENDENT mA TRIM
Use these features if the device connected to the HYDRO+ mA output
terminals is out of calibration, yet device recalibration is impractical.
Use of these features does not affect the mA Value / Transducer (P203)
value displayed.
P214 4 mA TRIM
Adjust this value (in mA) as required to make the device connected
indicate 4.000 mA when this parameter is accessed.
values: -1.00 to 1.000
P215 20 mA TRIM
Adjust this value (in mA) as required to make the device connected indicate
20.00 mA when this parameter is accessed.
values: -1.00 to 1.000