RATE PARAMETERS (P700 to P707)
P700 MAX FILL RATE
Adjust the HYDRO+ response to increases in the actual material level
(or advance to a higher Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel filling rate.
This value, in Units (P005) or % of Span (P007) per minute, is automatically
altered when Measurement Response (P003) is altered.
values: 0.000 to 9999
P701 MAX EMPTY RATE
Adjust the HYDRO+ response to decreases in the actual material level
(or advance to a lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate.
This value, in Units (P005) or % of Span (P007) per minute, is automatically
altered when Measurement Response (P003) is altered.
values: 0.000 to 9999
P702 FILLING INDICATOR
Enter the fill rate required to activate the LCD Filling indicator.
This value (in Units (P005) or % of Span (P007) per minute) is automatically
set to 10% of the Max Fill Rate (P700).
values: -999 to 9999
P703 EMPTYING INDICATOR
Enter the empty rate required to activate the LCD Emptying indicator.
This value (in Units (P005) or % of Span (P007) per minute) is automatically
set to 10% of the Max Empty Rate (P701) .
values: -999 to 9999