SCANNING PARAMETERS (P726 to P728)
P726 (G) LEVEL SYSTEM SYNC
Use this feature if another level measurement system is mounted
near the HYDRO+.
See Interconnection/Level System Synchronization.
values: 0 = not required
1 = synchronize level monitors (preset)
P727 (G) SCAN DELAY
This feature may only be used for "differential" or "average" Operation
(P001 = 4 or 5), to adjust the delay before the next point is scanned.
Enter the amount of delay in seconds. This value is automatically altered
when Measurement Response (P003) is altered.
values: -999 to 9999
P728 SHOT DELAY
Use this feature if transient acoustic noise within the vessel is causing
measurement difficulties.
Enter the delay (in seconds) between transmit pulse shots.
values: 0.1 to 4.0 (preset = 0.5 seconds)
P729 SCAN TIME
View the elapsed time (in seconds) since the point displayed was last
scanned. This value may be viewed as an Auxiliary Reading in the RUN
mode, and is particularly useful when "differential" or "average" Operation
(P001 = 4 or 5) is selected.
values: 0.000 to 9999