READING PARAMETERS (P060 to P062)
Alter the following parameters to:
a) change the number of decimal places displayed.
b) convert the Reading to alternate units.
c) reference measurements to other than Empty (P006) or Span (P007).
P060 DECIMAL POSITION
Enter the maximum number of Reading decimal places to be displayed.
In the RUN mode, the number of decimal places displayed is automatically
adjusted (if necessary) to prevent the number of Reading digits from
exceeding display capabilities.
This value is automatically altered when Units (P005) and/or Max Volume
(P051) is altered.
values: 0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P061 CONVERT READING
Enter the value to multiply the Reading by, (before display).
This feature is preset to 1.000 (no conversion).
e.g. If the Reading is displayed in feet, to display in yards, enter 3.
Avoid entering a value that, when multiplied by the maximum
current Reading, could exceed 5 digits before the
Decimal Position.
values: -999 to 9999
PARAMETERS
PL-507 67