PROFILE POINTER PARAMETERS
When a Profile Pointer Parameter is accessed, the Echo Lock Window scope display
changes to a Profile Pointer display. The Profile Pointer may be moved to a number of
points on the Echo Profile, to gain specific information dependent upon the Profile
Pointer Parameter used.
To move the Profile Pointer to a specific point, enter the desired value. The Profile
Pointer will move to the nearest acceptable Echo Profile point. The Profile Pointer is
preset to "0".
Alternatively, to scroll the Profile Pointer along the Echo Profile...
1. to display the Auxiliary Function symbol,
2. or to move the Profile Pointer to the left or right respectively.
When the Profile Pointer Parameters are exited and is pressed or the RUN mode
is entered, the Profile Pointer display automatically changes back to the Echo Lock
Window display.
P817 (V) PROFILE POINTER TIME
Observe the time (in ms) from the transmit pulse to the Profile Pointer.
values: 0.000 to 9999
P818 (V) PROFILE POINTER DISTANCE
Observe the distance (in P005 Units) between the transducer
face and the Profile Pointer.
values: 0.000 to 9999
P819 (V) PROFILE POINTER AMPLITUDE
Observe the amplitude (in dB above 1 uV) of the Echo Profile at the
Profile Pointer position.
values: 0 to 99
PARAMETERS
PL-507 137