P823 REFORM ECHO
Use this feature, when monitoring solids (P002 = 2), if the reported level
fluctuates slightly, though the monitored surface is still).
Enter the amount (in ms) of long shot Echo Profile smoothing required to
eliminate jagged peaks in the Echo Profile.
When a value is keyed in, the nearest acceptable value is entered.
values: 0 = off (preset), greater = wider
P825 ECHO MARKER TRIGGER
Use this feature if the reported material level fluctuates slightly, due to a
variable rise in the leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock Window
intersects the Echo Profile at the sharpest rising portion of the Echo Profile
representing the true echo. This value is preset to 50%.
values: 5 to 95
PARAMETERS
PL-507 139