P920 READING MEASUREMENT
The Reading corresponds to all associated programming after
is pressed or during simulation.
P921 MATERIAL MEASUREMENT
The Reading corresponds to the distance between Empty (P006) and the
monitored surface after is pressed, or during simulation.
P922 SPACE MEASUREMENT
The Reading corresponds to the distance between the monitored surface
and Span (P007) after is pressed, or during simulation.
P923 DISTANCE MEASUREMENT
The Reading corresponds to the distance between the monitored surface
and the transducer face, after is pressed or during simulation.
P924 VOLUME MEASUREMENT
The Reading corresponds to the calculated vessel capacity utilized
(not remaining), after is pressed, displayed in Max Volume (P051)
units or % of Max Volume.
P925 FLOW MEASUREMENT
The Reading corresponds to the calculated flowrate, after is pressed,
in Max Flow (P604) units or % of Max Flow.
P926 HEAD MEASUREMENT
The Reading corresponds to
Head
(the distance from Min Head (P605)
to the monitored surface), after is pressed, in Units (P005) or % of
Span (P007).
P927 DISTANCE PERCENT
Same as P923, plus alternate reading in % .
PARAMETERS
PL-507 147