PROGRAMMING
LCD TOTALIZER
P622 In/Out Correction = 1 (preset, auto total inflow/discharge adjust)
P630 LCD Total Factor = 0 (preset, display total in Max Volume units)
P633 LCD Total Decimal = 3 (e.g. display 3 decimal places)
REMOTE TOTALIZER (optional)
P111 Relay Function = 40 (totalizer) for RL5
P640 Relay Total Factor = 0 (preset, pulse every 1 x 10
0
Max Volume units)
P645 Relay On Time = 0.2 seconds (preset, adjust if necessary to suit totalizer)
OPERATION
1. Alarms and/or controls operate as programmed by other
Control Application programming examples.
2. The totalizer relay energizes for (P645) seconds for every (P640) volume units.
3. The 4-20 mA output is proportional to volume (per Volume Calculation).
4. to display 8 digit total volume pumped value.
5. To view pump information in the RUN mode...
and then the pump # (to view the pump running hours total)
and hold the pump # (to view the number of pump starts total)
APPLICATIONS