PUMP CONTROL MODIFIERS (P130 to P134 and P136)
P130 (G) RUN ON INTERVAL
Use this feature to periodically have pumps continue running for a specified
time (Run On Duration, P131) to discharge sediment.
Sets the period, in hours, during which a pump run-on may occur.
values: 0.000 to 9999 (preset = 0.000)
P131 (G) RUN ON DURATION
Enter the duration of pump run-on, in seconds. Only one run-on is allowed
per interval (P130).
Choose a value long enough to clean out the vessel bottom, yet short
enough not to run the pump dry (if to do so may damage the pump).
values: 0.0 to 9999 (preset = 0.0)
P132 (G) START DELAY
Use this feature to reduce the power (mains) surge that would be
generated if multiple pumps were to start simultaneously.
Enter the time to elapse (in seconds) after a pump has started before
the next pump is permitted to start (if called for).
values: 0.0 to 9999 (preset = 10 seconds)
P133 (G) POWER RESUMPTION DELAY
Use this feature to reduce the power (mains) surge that would occur if
pumps were to start immediately on power resumption.
Enter the time to elapse after power resumption (following a power
interruption) before pumps are permitted to start.
values: 0.0 to 9999 (preset = 10 seconds).