PUMP RECORDS (P310 to P312)
Use these features to identify pump usage.
When any of these features are accessed, the Point Type display changes to the
Relay Symbol and the Relay Number (corresponding to HYDRO+ terminals) is
displayed in the Point Number field.
These features are enabled if the associated Relay Function (P111) is set for any
"pump control" feature. The value displayed pertains to the pump connected to
the associated HYDRO+ terminals.
Enter "0" (if desired) when these parameters are accessed, to reset these features
(perhaps when a new replacement pump is installed). Alternatively, enter any
other (applicable) value (perhaps when a used replacement pump is installed).
During operation, these values are dynamic (continuously changing). Once per
hour, the dynamic value is stored in non-volatile EEPROM memory. Therefore, in
the event of a power interruption, upon power resumption, the value will be
correct to within at least 60 minutes prior to the interruption.
If desired, connect a backup dc power source to the HYDRO+ to ensure the Pump
Records are not affected by an ac power interruption.
(See INSTALLATION Interconnection / Power).
P310 PUMP HOURS
View the accumulated "ON" time for the displayed Relay Number.
This value is displayed with a floating decimal point. (i.e. the more figures
displayed before the decimal, the fewer displayed after).
values: 0.000 to 9999
P311 PUMP STARTS
View the accumulated number of times the displayed Relay
Number has been "ON".
values: 0 to 9999
P312 PUMP RUN ONS
View the accumulated number of times the displayed Relay Number
has been held "ON" via Run On Interval (P130).
values: 0 to 9999
INSTALLATION
PARAMETERS
PL-507 97