MP 26 Transmitter Installation and Calibration Manual
Minebea Intec
Mounting & Dismounting the Device
The instruments can be mounted directly side by side. For mounting and dismounting, a
minimum of 8 cm free space above and below the units should be provided.
For mounting, simply clip the unit onto the top-hat rail from the top and click it into
position. To dismount the unit, pull the bottom catch downwards using a screwdriver and
remove the unit upwards
Note:
The transmitter MP 26 does not contain any maintenance parts, i.e. the unit need not be opened by the
customer.
The unit may be operated only in environments for which it is suitable due to its protection type. The housing
ventilation slots must not be covered.
In plants susceptible to transient voltage peaks, the instruments must be equipped with additional protective
filters or voltage limiters!
CAUTION!
The instrument contains electrostatically sensitive components.
To maintain contamination degree 2 according to EN 61010-1, the instrument must not be installed below
contactors or similar units from which conducting dust or particles might settle.