FX-2000 Series Installation and Operation Manual
43
Relay Module (RM-1008(A)) Terminal Connections
Relays are available as shown below in Figure 36.
Figure 35: Hardwire Relay Module Terminal Connections
Notes:
All relay circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
All relay circuits must be connected to a listed power limited source of supply.
ATTENTION:
Do not connect 120 VAC directly to these relays.
RLY 1
AUX RELAY
1
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 2
AUX RELAY 2
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 3
AUX RELAY 3
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 4
AUX RELAY 4
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
COM
RLY 5
NO
NC
AUX RELAY 5
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 6
AUX RELAY 6
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 7
AUX RELAY 7
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RLY 8
AUX RELAY 8
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC