FX-2000 Series Installation and Operation Manual
69
FX-2000 Series Compatible Synchronized Modules and Strobes
Synchronization for strobes can be accomplished by using Sync Modules.
Manufacturer Brand Sync. Module Strobe Model
Max. Strobe /
NAC
Amseco / Potter Mircom SDM 240 FHS-240-110 15
Gentex Corp. Secutron AVS44 R MRA-HS3-24ww 20
SpectrAlert System Sensor MDL P1224 MC 25
Wheelock Wheelock DSM 12/24 NS-24 MCW -FW 25
Faraday Faraday 5406 6234B-14-24 26*
Notes:
1. * Strobes and horns must be connected to separate circuits since the horn is a non-synchronized
audible appliance.
2. Do not mix and match sync module with strobes from different manufacturers because each
manufacturer uses different synchronization protocols.