FX-2000 Series Installation and Operation Manual
1
Introduction
About the FX-2000
Mircom's cost-effective FX-2000 Intelligent Analog Fire Alarm Control Panel is a flexible and easy-to-use analog
system. The FX-2000 base panel consists of one intelligent analog loop controller capable of supporting 99 analog
sensors and 99 addressable modules that can be wired in Class A (Style 6 or 7) or Class B (Style 4). Loop adder
modules are available for additional addressable loops. The ALC-198S provides one additional addressable loop,
and the ALC-396S provides two addressable loops each capable of supporting 99 analog sensors and 99
addressable modules. In addition, the base panel supports 16 conventional adder modules such as the DM-1008A
Initiating Circuit Module, SGM-1004A Indicating Circuit Module, and the RM-1008A Relay Circuit Module. The base
panel also includes 4 Class A/B (Style Z/Y) indicating circuits rated at 1.7 amperes each, and either a 6- or 12-
ampere power supply. The ALC-H16 adder board provides expansion for 16 additional hardwire/conventional
modules.
Overall Features
• Large System Capacity and Modular Design.
• Each Analog Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be
wired as Class A (Style 6 or 7) or Class B (Style 4).
• The Base System supports 16 conventional hardwire Adder Modules.
• 6 or 12 Ampere Power Supply.
• Four Class A/B (Style Z/Y) Indicating Circuits rated at 1.7 Amperes each, which can be configured as Audible or
Visual (silenceable or non-silenceable circuits). Audibles may be steady, Temporal Code, California Code, or
March Time.
• Indicating circuits may be configured to provide additional auxiliary power or resettable auxiliary power.
• Fault isolators are present on all in panel addressable loops.
• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-Man Walk Test.
• Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an interface to the Mircom RTI
Remote Trouble Indicator.
• RS-485 Interface for Remote Multiplex Annunciators.
• Three Level Password Protection with field settable definition which enables the installer to determine what
functions are accessible for each of the three levels of pass
• Four Queues for Alarm, Supervisory, Trouble, and Monitor, with LED indicators and selector keys.
• Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and Common Trouble.
• RS-232 Port for remote system printer or “CRT terminal”.
• Two Event History Logs; one for Alarm related events and one for all events.
• Front Panel Auto-Configure and / or Personal Computer Configuration.
• Large 4 line by 20 character alphanumeric, back-lit LCD Display with user-friendly menu system.
• Common Controls and Indicators for System Reset, Lamp Test, Fire Drill, Signal Silence, General Alarm,
• Acknowledge, AC On, Pre-Alarm, and Ground Fault.
• Two Spare configurable Keys and LED Indicators.
• 16 Zone configurable LED (bi-coloured) Annunciator with slide-in labels for Zone Description.
• Provides drift compensation for photoelectric smoke detectors
• Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1 to 4 digits, each digit
consisting of 1-15 pulses on the signal)
• Selection for Canadian (ULC) or USA (ULI) requirements for Smoke Sensor sensitivity.
• Extensive transient protection.
• Surface Mountable Enclosures with removable doors for easy installation and service. Flush Trims Available.
• Removable Terminal Blocks for easy wiring and service.
• Loop Adder modules ALC-198S and ALC-396S for expanding addressable loops by 1 and 2 respectively.
• Adder module ALC-H16 hardwire loop interface board for expanding conventional input, output, relay capability.