5 - 28
5. PARAMETERS
5.2.3 Using forward/reverse rotation stroke end to change the stopping pattern
The stopping pattern is factory-set to make a sudden stop when the forward/reverse rotation stroke end is
made valid. A slow stop can be made by changing the parameter No.22 value.
Parameter No.22 setting Stopping method
0
(initial value)
Sudden stop
Position control mode
Internal speed control mode
: Motor stops with droop pulses cleared.
: Motor stops at deceleration time constant of zero.
1
Slow stop
Position control mode
Internal speed control mode
: The motor is decelerated to a stop in accordance with the
parameter No.7 value.
: The motor is decelerated to a stop in accordance with the
parameter No.12 value.
5.2.4 Alarm history clear
The servo amplifier stores one current alarm and five past alarms from when its power is switched on first. To
control alarms which will occur during operation, clear the alarm history using parameter No.16 before starting
operation.
Clearing the alarm history automatically returns to "
0 ".
After setting, this parameter is made valid by switch power from OFF to ON.
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
Parameter No.16