230
13 PROGRAMMING
13.3 When the Module Is Connected to a Head Module
Operation of the flexible high-speed I/O control module at disconnection
For details on the Y signal status of when a head module is connected, refer to the following.
MELSEC-L CC-Link IE Field Network Head Module User's Manual
"Hardware logic control
valid/invalid during
disconnecting"
"Error Time Output Mode" Operation of the flexible high-speed I/O control module
Y signal status Hardware logic
operation
External output
status
Valid Hold Held Continued Output according to the
operation result by the
hardware logic control
Clear Turned off Stop Output set in "Error-time
Output Mode" of the
external output block
Invalid Hold Held Continued Output according to the
operation result by the
hardware logic control
Clear Turned off Continued