APPENDICES
Appendix 1 Details of I/O Signals
241
A
Hardware logic control flag (X4)
While the hardware logic operates, Hardware logic control flag (X4) is on.
ON of Hardware logic control flag (X4)
In the following status, this signal turns on.
When Hardware logic control start request (Y4) is turned on
When the hardware logic control start request is issued with the configuration tool
OFF of Hardware logic control flag (X4)
In the following status, this signal turns off.
When the power supply is turned on
When the CPU module is reset
When Hardware logic control stop request (Y5) is turned on (If Hardware logic control start request (Y4) and Hardware logic
control stop request (Y5) are turned on at the same time, Hardware logic control stop request (Y5) takes priority and
Hardware logic control flag (X4) does not turn on.)
When the hardware logic control stop request is issued with the configuration tool
From when the "Write to Module (execution memory)" or "Write to Module (execution + flash ROM)" is executed with the
configuration tool until the hardware logic control restarts
When the simulation is executed with the configuration tool
When Hardware logic control stop flag at disconnection (X7) turns on
When a stop error occurs in the CPU module
Performed in the flexible high-speed I/O control module
Performed in the program
OFF
ON
OFF
ON
OFF
ON
Hardware logic control
start request (Y4)
Hardware logic control
stop request (Y5)
Hardware logic control
flag (X4)
Operating status Stopped Operating Stopped