EasyManua.ls Logo

Mitsubishi Electric WS0-CPU0 - Page 26

Mitsubishi Electric WS0-CPU0
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 3
23
Version, compatibility and features
Device WS0-CPU
WS0-XTIO/
WS0-XTDI
Setting and
Monitoring Tool
Ethernet interface module V1.11
(Revision 1.xx)
– V1.2.0
CC-Link interface module V1.11
(Revision 1.xx)
– V1.2.1
ROHS conformity WS0-XTIO V1.01
*2
*1 “–” means “any” or “not applicable”.
*2 All other modules from product launch onwards.
You can find the firmware version on the type label of the MELSEC-WS modules in
the field Firmware version.
In order to use modules with a newer firmware version, a new Setting and
Monitoring Tool version is required. For CPU0/1 V2.01 and XTIO/XTDI V2.00
Setting and Monitoring Tool V1.3.0 or higher is required. This has to be considered
when devices are to be replaced in existing systems.
You will find the firmware version of the MELSEC-WS modules in the hardware
configuration view of the Setting and Monitoring Tool when the system is online or
in the report if the system has been online before.
The version of the Setting and Monitoring Tool can be found in the Extras menu
under About.
For the acquisition of the newest version of the Setting and Monitoring Tool, please
contact your local Mitsubishi representative.
The function package (Revision 1.xx or Revision 2.xx) must be selected in the
Setting and Monitoring Tool hardware configuration. Function package Revision
2.xx is available with Setting and Monitoring Tool 1.3.0 and higher.
In order to use function package Revision 2.xx, the respective module must have at
least firmware version V2.00.0. Otherwise you will receive an error message when
you try to upload a configuration using Revision 2.xx to a module with a lower
firmware version.
Newer modules are downward compatible so that any module can be replaced by a
module with a higher firmware version.
The same firmware version and function package revision as those of the module
used must be set to the new project after a project stored in the memory plug is
modified.
You will find the device’s date of manufacture at the bottom of the type label in the
format yywwnnnn (yy = year, ww = calendar week, nnnn = continuos serial number
in the calendar week).
Note

Table of Contents