Menu 8.3.7 [U] Return
Return to Menu 8.3.0.
Menu 8.5.0 [U] Period settings
Time periods for heating and hot water production are set in
the sub-menus for this menu.
Menu 8.5.1 [U] Period time
You can set the length of cycle time for water production and
heating in case there is demand for both.
Setting range: 5 – 60 min
Default value: 60 min
Menu 8.5.2 [U] Max time for HW
Here you select operation period for hot water of the period
time. (8.5.1)
Setting range: 0 – 60 min
Default value: 40 min
Menu 8.5.3 [U] Return
Return to Menu 8.5.0.
Menu 8.6 [N] Return
Return to Menu 8.0.
9.0 [S] Service menus
Menu 9.1.0 [S] Heat pump settings
Settings for outdoor unit are made in the sub-menus to this
menu.
Menu 9.1.1 [S] DM start heating
Degree minute setting for start of heat pump, heating.
Setting range: -120 – 0
Default value: -60
Menu 9.1.2 [S] DM start cooling
Degree minute setting for start of heat pump, cooling.
Setting range: 0 – 120
Default value: 60
Menu 9.1.3 [S] Stop Temp. heat low
Lowest limit of the heat pump’s working range during heating.
It stops below this outdoor air temperature.
The heat pump is permitted to start again when the outdoor air
temperature increases by two degrees above the set value.
Setting range: -25 – 43 °C
Default value: -25 °C
Menu 9.1.4 [S] Stop Temp. heat high
Highest limit of the heat pump’s working range during heating.
It stops above this outdoor air temperature.
The heat pump is permitted to start again when the outdoor air
temperature decreases by two degrees below the set value.
Setting range: -25 – 43 °C
Default value: 43 °C
Menu 9.1.5 [S] Stop temp. cool low
Lowest limit of the heat pump’s working range during cooling.
It stops below this outdoor air temperature.
The heat pump is permitted to start again when the outdoor air
temperature increases by two degrees above the set value.
Setting range: 10 – 43 °C
Default value: 10 °C
Menu 9.1.6 [S] Stop temp. cool high
Highest limit of the heat pump’s working range during cooling.
It stops above this outdoor air temperature.
The heat pump is permitted to start again when the outdoor air
temperature decreases by two degrees below the set value.
Setting range: 10 – 43 °C
Default value: 43 °C
Menu 9.1.7 [S] Time bet. starts
Minimum time interval in minutes between compressor starts
in the heat pump.
Setting range: 0 – 60 min
Default value: 0 min