EasyManuals Logo

Mitsubishi MT300 User Manual

Mitsubishi MT300
305 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
-
158
-
Service
'10 HM-T-149
NO
YES
NO
NO
YES
NO
It may need to add external
circulation pump.
Consult installer.
Set on correct value.
YES
YES
NO
Fix it and recharge refrigerant.
Attach wind protection on
outdoor unit.
Charge correct amount of refrigerant
YES
Remove the blockage.
Clean the filter.
YES
NO
YES
Is the water flow rate bigger than
minimum flow rate?
*Go to “No” for alarm 16.
It occurs in case water flow is
insufficient during defrost.
Is the water flow setting done
correctly?
Is the heating circuit clogged
in somewhere else?
Is the particle filter clogged?
Is the outdoor unit;
1installed where wind blows
into directly
and
2not equipped with wind
protection?
Is the refrigerant charged
correctly according to piping
length?
Does the refrigerant leak from
somewhere else?
14, 16 - Aborted defrost
Troubleshooting guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MT300 and is the answer not in the manual?

Mitsubishi MT300 Specifications

General IconGeneral
BrandMitsubishi
ModelMT300
CategoryHeat Pump
LanguageEnglish

Related product manuals