Programmable digital outputs
11 to 15
101
Programmable digital outputs 11 to 15
Programmable digital outputs 11 to 15 are open collector tran-
sistor outputs (a Fig. 98), to which you can connect, for
example, relays. These outputs can be used for various functions,
for example to signal when a determined frequency setpoint is
reached or when a fault occurs.
The terminal functions for programmable digital outputs 11 to 15
are configured under PNU C021 to C025 respectively, i.e.
PNU C021 defines the function of digital output 11, PNU C022 the
function of digital output 12, etc.
Table 17: Digital outputs 11 to 15
For a detailed description of the output functions, see the pages
listed in Table 18.
Table 18: Functions of the digital outputs
Programmable digital outputs 11 to 15 are configured by default
as make contacts.
Optionally, you can configure the digital outputs as break (NC)
contacts. To do this, enter 01 under PNU C031 to C35 (correspon-
ding to digital outputs 11 to 15).
Table 19: Configuration of digital outputs as make contacts
Figure 98: Digital output
Transistor output: up to 27 V H, 250 mA
PNU Ter-
minal
Adjustable in RUN
mode
Value WE
Normal Extended
C021 11 j a Table 18 01
C022 12
00
C023 13
03
C024 14
07
C025 15
08
Value Function
Description a Page
00 RUN Operation 104
01 FA1
Frequency setpoint reached 102
02 FA2
Frequency exceeded 102
03 OL Overload signal 105
04 OD
PID control deviation
exceeded
106
05 AL
Fault 107
06 FA3
Frequency (within range)
reached
102
07 OTQ
Torque reached (exceeded) 110
08 IP Mains failure, immediate stop 113
F 27 V H, 250 mA
11, 12, 13, 14, 15
CM2
24 V
– +
09 UV Undervoltage signal 113
10 TRQ
Torque limitation 111
11 RNT
Running time exceeded 114
12 ONT
Mains On time exceeded 114
13 THM Motor thermal overload 115
19 BRK
Release brake 108
20 BER
Brake fault 108
21 ZS
Zero speed 109
22 DSE
Speed deviation exceeded
1)
23 POK Positioning
1)
24 FA4 Frequency exceeded 102
25 FA5
Frequency setpoint reached 102
26 OL2
Overload signal 2 105
1) a Manual AWB8230-1431.. for encoder module DE6-IOM-ENC
PNU Ter-
minal
Value Adjustable in
RUN mode
Function WE
Nor-
mal
Exten-
ded
C031 11 00 or
01
j 00: Make
contact
01: Break
contact
00
C032 12
C033 13
C034 14
C035 15
Value Function
Description a Page