Setting Parameters
01/02 AWB8230-1415GB
176
User-defined parameters parameter group U
With parameter group U (user), you can group any parameters for
quick access. You can save up to twelve editable and display para-
meters in this group, to give you quick access to your most
frequently used parameters. The default value of the U parameters
is no (no function). You do not have to confirm your selection
with the ENTER key. The most recently selected parameter is saved
automatically.
Example: Saving acceleration time 1 (PNU F002) in PNU U001:
The DV6 is in the display mode and the RUN lamp is lit.
X Press the PRG key.
The DV6 changes to programming mode, the PRG lamp lights up
and d001 or the most recently modified parameter appears on the
display.
X Press the DOWN key until U--- appears on the display.
X Press the PRG key. U001 appears on the display.
X Press the PRG key. no appears on the display.
X Press the UP or DOWN key until F002 appears on the display.
X Press the PRG key.
The set acceleration time 1 in seconds appears on the display
(default value: 30).
X You can change the set value with the UP and DOWN arrow
keys.
There are now two possibilities:
X Accept the set value by pressing the ENTER key.
X To reject the set value, press the PRG key.
F002 appears on the display. PNU F002 is now saved under
PNU U001.
X Press the PRG key. U001 appears on the display.
X Press the PRG key. U--- appears on the display.
X Press the UP or DOWN key until d001 appears on the display.
X Press the PRG key. The DV6 changes to display mode and
displays the set frequency.
You can now change PNU F002 by calling up PNU U001:
X Go to parameter group U. The display shows U---.
X Press the PRG key. U001 appears on the display.
X and press the PRG key again. F002 appears on the display.
You can now change the value of PNU F002.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
U001 User-defined
parameters
j PNU A001 to
P032
Under PNU U001 to U012, you can save frequently used
parameters.
no
U002
U003
U004
U005
U006
U007
U008
U009
U010
U011
U012