Mains contactors
195
Mains contactors
h
The mains contactors listed here assume the network’s
rated current (I
LN
) without mains choke or mains filter.
Their selection is based on the thermal current (AC-1).
Caution!
Jog mode must not be used through the mains contactor
(rest period f 180 s between switching off and on)
DV6-340- DV6 phase current Mains contactor
Open/enclosed Model
I
LN
[A] I
th
AC-1 [A]
075 2.8 20/16 DILEEM
1K5 4.2
2K2 5.8
4K0 9.5
20/16 DIL00M
5K5 13
7K5 18
11K 25
35/30 DIL0M
15K 35
18K5 42
55/44 DIL1M
22K 53
30K 63
90/80 DIL2M
37K 83
45K 99
100/– DIL3M80
55K 121
160/– DIL4M115
75K 164
90K 194
225/– DILM185
110K 239
250/– DILM225
132K 286
300/– DILM250