The DV6 series frequency inverters have programmable parame-
ters. In the free Setpoint columns below, you can list the changes
you have made from the default settings.
PNU Function Units Default Page Setpoint
A001 Frequency setpoint input through
00: Potentiometer
01: Analog inputs O, O2 or OI
02: PNU F001 or A020
03: RS 485 serial interface
04: Optional module in slot 1
05: Optional module in slot 2
01 123
A002 Start signal definition through
01: Input FWD/REV
02: ON key
03: RS 485 serial interface
04: Optional module in slot 1
05: Optional module in slot 2
01 124
A003 Base frequency [Hz] 50 125
A203 Base frequency (second parameter set) [Hz] 50 125
A303 Base frequency (third parameter set) [Hz] 50 125
A004 Maximum end frequency [Hz] 50 125
A204 Final frequency (second parameter set) [Hz] 50 125
A304 End frequency (third parameter set) [Hz] 50 125
A005 AT selection
00: AT input switches between analog input O and
OI
01: AT input switches between analog input O and
O2
00 61
A006 O2 selection
00: O2 signal only
01: Sum of signals at O2 and O/OI without direction
reversal
02: Sum of signals at O2 and O/OI with direction
reversal
00 61
A011 Frequency at minimum setpoint value (terminal O-L) [Hz] 0.00 63
A012 Frequency at maximum setpoint value (terminal O-L) [Hz] 0.00 63
A013 Minimum setpoint value (terminal O-L) [%] 0 63
A014 Maximum setpoint value (terminal O-L) [%] 100 63
A015 Starting frequency (terminal O-L)
00: Apply PNU A011 to motor
01: Apply 0 Hz to motor
01 63
A016 Analog input filter time constant 863
A019 Fixed frequency selection
00: Binary selection through digital inputs FF1 to FF4
01: Bitwise selection through digital inputs SF1 to
SF7
00 70
A020 Frequency setpoint definition (PNU A001 must be 02) [Hz] 0.00 70
A220 Frequency setpoint definition (PNU A001 must be 02)
(second parameter set)
[Hz] 0.00 70
A320 Frequency setpoint definition (PNU A001 must be 02)
(third parameter set)
[Hz] 0.00 70