Programming the control
signal terminals
01/02 AWB8230-1415GB
58
Analog outputs AM, AMI and FM
The analog outputs provide various physical variables, which you
can select and some of which you can adjust to meet your specific
needs. Terminals AM, AMI and FM are connected to chassis
through terminal L.
Voltage output (AM)
The AM terminal provides the variables listed in the table below in
the form of a 0 to 10 V voltage signal.
X In PNU C028, specify the variable which the AM terminal is to
provide.
X In PNU B080, specify the gain factor and in PNU C086 the
offset.
PNU Function Adjustable in RUN mode Value Function WE
Normal Extended
b080 Gain, AM
terminal
j j 0 to 255 Gain of the voltage output 180
C028 Output, AM
terminal
j 00 Output frequency: 0 Hz to end frequency PNU A004
(a Section Maximum end frequency, Page 125)
00
01 Output current: 0 to 200 %
02 Torque: 0 to 200 %
04 Output voltage: 0 to 100 %
05 Inverter input power: 0 to 200 %
06 Thermal load ratio: 0 to 100 %
07 Ramp frequency: 0 Hz to end frequency PNU A004
(a Section Maximum end frequency, Page 125)
C086 Offset, AM
terminal
j j 0 to 10 V Voltage increase 0.0