EasyManua.ls Logo

Moeller DV6-340 Series - Standard form for user defined parameter settings

Moeller DV6-340 Series
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
01/02 AWB8230-1415GB
196
Mains choke
Figure 174: DE4-LN... mains chokes
h
When the frequency inverter is working at its rated current
limit, the mains choke causes a reduction of the frequency
inverters maximum output voltage (U
2
) to about 96 % of
mains voltage (U
LN
).
DV6-340- Mains current
(I
LN
) of the DV6
without mains
choke
Assigned
mains choke
075 2.8 DE4-LN3-075
1K5
4.2 DE4-LN3-2K2
2K2
5.8 DE4-LN3-3K0
4K0
9.5 DE4-LN3-4K0
5K5 13 DE4-LN3-7K5
7K5
18 DE4-LN3-11K
11K 25 DE4-LN3-15K
15K
35 DE4-LN3-15K
18K5
42 DE4-LN3-22K
22K 53 DE4-LN3-30K
30K
63 DE4-LN3-45K
37K
83 DE4-LN3-45K
45K
99 DE4-LN3-55K
55K
121 DE4-LN3-75K
75K
164 DE4-LN3-90K
90K 194 DDK3,2-9,2
110K
239 DDK4,0-9,2
132K
286 DDK4,0-9,2
h
For technical data for the DE4-LN series mains chokes, see
installation instructions AWA8240-1711, for those of the
DDK series, refer to the main Industrial Switchgear cata-
logue.
h
Mains chokes reduce the magnitude of the current harmo-
nics up to about 30 % and increase the lifespan of
frequency inverters and upstream-connected switching
devices.