Parameter protection
159
Parameter protection
Under PNU b031, you can specify whether you want to use the
normal or extended parameter setting features in RUN mode. If
you set the value 10 under PNU b031, further parameters are avai-
lable which can be modified in the RUN mode. These additional
parameters are marked j in the Extended column.
.
The five following methods of parameter protection are available:
Adjustable in RUN mode
Normal Extended
j
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b031 Software
parameter
protection
j 00 Parameter protection through SFT input;
all functions inhibited
01
01 Parameter protection through SFT input;
input through PNU F01 possible
02 Parameter protection without SFT input;
all functions inhibited
03 Parameter protection without SFT input;
input through PNU F01 possible
10 Extended parameters adjustable in RUN mode