Programming the control
signal terminals
01/02 AWB8230-1415GB
62
Matching of terminals O, O2 and OI
With PNU C081 to C083 and PNU C121 to C123, you can adapt
the analog setpoint signals at terminals O, O2 and OI to your
requirements:
• Terminal O: 0 to +10 V
– Setpoint signal matching: PNU C081
– Zero point matching: PNU C121
• Terminal O2, –10 V to +10 V
– Setpoint signal matching: PNU C083
– Zero point matching: PNU C123
• Terminal OI: 4 to 20 mA
– Setpoint signal matching: PNU C082
– Zero point matching: PNU C122
Caution!
These parameters are not reset to their default values
during initialization.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C081 Matching of
terminal O
j j 0 to 65530 Here, you can match the setpoint signal (0 to +10 V)
supplied at analog input O with reference to the output
frequency.
Depen-
ding on
DV6
C082 Matching of
terminal OI
Here, you can match the setpoint signal (4 to 20 mA)
supplied at analog input OI with reference to the output
frequency.
C083 Matching of
terminal O2
Here, you can match the setpoint signal supplied at analog
input O2 (–10 V to +10 V) with reference to the output
frequency.
C121 Zero-point
matching,
terminal O
0 to 6553
(65530)
Here, you can match the setpoint signal (0 to +10 V)
supplied at analog input O with reference to the zero point.
C122 Zero-point
matching,
terminal OI
Here, you can match the setpoint signal (4 to 20 mA)
supplied at analog input OI with reference to the zero
point.
C123 Zero-point
matching,
terminal O2
Here, you can match the setpoint signal (–10 V to +10 V)
supplied at analog input O2 with reference to the zero
point.