01/02 AWB8230-1415GB
Programmable digital inputs
1to8
93
Setpoint value through keypad (OPE)
When you activate the digital input configured as OPE, an Enable
signal must be issued with the ON key on the keypad. If, for
example, you have entered the value 01 under PNU A001
(frequency setpoint input through analog input) and the value 01
under PNU A002 (start signal through digital input), these settings
become invalid as soon as you activate the OPE input. PNU A002
then contain the value 02 (start signal through ON key) and the
setpoint frequency under PNU A020 or PNU F001 becomes active.
If you activate the OPE input while the inverter is in RUN mode, it
decelerates and can then be started with the ON key on the device.
If the start signal is still active, the frequency inverter accelerates
to the previously set frequency again as soon as you deactivate the
OPE input.
X Program one of the digital inputs 1 to 8 as OPE by entering the
value 31 under the corresponding PNU (C001 to C008).
Figure 84: Digital output 11 configured as OPE (setpoint definition
through keypad)
OPE
FWD
P24FW1
Figure 85: Function chart for OPE (setpoint definition through
keypad)
f
O
: Output frequency
PNU A020/
F001
OPE
FW
f
o
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A001 Defined
frequency
setpoint
00 Definition with the potentiometer on the keypad 01
01 Definition through analog input O (0 to 10 V), O2 (g10 V) or
OI (4 to 20 mA)
02 Definition through PNU F001 and/or PNU A020
03 Definition through RS 485 serial interface
04 Setpoint definition through the optional module in slot 1
05 Setpoint definition through the optional module in slot 2
A002 Start signal
01 The motor start signal is issued through the FW input or a
digital input configured as REV.
01
02 The motor start signal is issued by the ON key on the keypad.
03 The motor start signal is issued through the RS 485
interface.
04 The motor start signal is issued through the optional module
in slot 1.
05 The motor start signal is issued through the optional module
in slot 2.