01/02 AWB8230-1415GB
Programmable digital outputs
11 to 15
105
Overload signal OL, OL2
The digital output configured as OL or OL2 is activated when a
freely selectable motor current is exceeded. The OL/OL2 output is
active as long as the motor current is higher than this threshold.
X If you configure a programmable digital output as OL, you must,
under PNU C041, enter the current at which, when exceeded,
the OL signal is activated.
X To configure a programmable digital output as OL2, define the
current under PNU C111 at which, when exceeded, the OL2
signal is activated.
X Then, program one of the digital outputs 11 to 15 as OL output
by setting the corresponding PNU (C021 to C025) to 03.
X Then, program one of the digital outputs 11 to 15 as OL2 output
by setting the corresponding PNU (C021 to C025) to 26.
By default, OL is assigned to digital output 13.
Figure 105: Digital output 11 configured as OL/OL2 (overload signal)
r
Figure 106: Function chart for OL (overload signal)/OL2
OL
24 V
50 mA
11CM2
12 13 14 15
–
+
OL
PNU C041
I
M
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C040 Overload alarm
signal
– j 00 Always 01
01 Only at constant speed
C041 Overload alarm
threshold
0 to 2 x I
e
1)
The current value entered here determines when the OL
signal is activated.
I
e
1)
C111 The current value entered here determines when the OL2
signal is activated.
1) Frequency inverter rated current
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616