Programming the control
signal terminals
01/02 AWB8230-1415GB
96
Three-wire control (STA STP F/R)
With digital inputs configured as STA, STP and F/R, you can
operate the DV6 frequency inverter with three switches:
STA: Start
STP: Stop
F/R: Reverse direction
X Program three of digital inputs 1 to 8 as STA, STP and F/R, by
entering the following values under the corresponding PNU
(C001 to C008):
STA: 20
STP: 21
F/R: 22
The DV6 frequency inverter accelerates to the setpoint frequency
entered under PNU A020.
X Under PNU A001, enter the value 02 (setpoint definition
through PNU A020).
X Under PNU A002, enter the value 01 (start signal through
digital inputs).
X Under PNU A020, enter the setpoint frequency.
If you want to start the inverter through the STA input, the STP
input must be activated (inverse function, fail-safe). The signal
must be applied for only a short time (pulse). If the STP input is
deactivated, the motor is stopped. If the F/R input (pulse) is acti-
vated, the motor direction is reversed.
Figure 89: Digital input 1 configured as STA (pulse start), digital input
2 as STP (Pulse stop) and digital input 3 as F/R (reverse
direction).
F/R
STA
STP
P24123
Figure 90: Function chart for STA (pulse start) STP (pulse stop) and
F/R (direction reversal)
F/R
STP
FWD
REV
STA
f
o
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A001 Defined
frequency
setpoint
00 Definition with the potentiometer on the keypad 01
01 Definition through analog input O (0 to 10 V), OI
(4 to 20 mA) or O2 (10 V to +10 V H)
02 Definition through PNU F001 and/or PNU A020
03 Definition through the RS 485 serial interface, terminals RP,
2 x SN and SP
04 Definition through optional card at slot 1
05 Definition through optional card at slot 2
A002 Start signal
01 The motor start signal is issued through digital inputs, for
example through the FW input or a digital input configured
as REV.
01
02 The motor start signal is issued by the ON key on the keypad.
03 The motor start signal is issued through the RS 485 inter-
face.
04 The motor start signal is issued through the optional module
in slot 2.
05 The motor start signal is issued through the optional module
in slot 2.
A020
A220
A320
Frequency
setpoint value
j j 0 to PNU A004 You can enter a frequency setpoint value. Set PNU A001 to
02 for this purpose.
0.0