01/02 AWB8230-1415GB
Programmable digital inputs
1to8
95
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A044
A244
A344
Voltage/
frequency
characteristic
00 V/f characteristic, linear 00
01 V/f characteristic, quadratic, for example fans
02 User-definable
03 Sensorless vector control (SLV)
1)
04 0 Hz SLV
1)
05 Vector control
1)
with optional DE6-IOM-ENC module
b040 Selection of
torque
limitation
j 00 Torque limitation in all four quadrants (PNU b041 to b044) 00
01 Changeover of torque limits through digital inputs
(TRQ1 and TRQ2)
02 Torque limit through analog input O (0 to 10 V)
03 Torque limit through optional module on slot 1
04 Torque limit through optional module on slot 2
b041 Torque limit,
first quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b042 Torque limit,
second
quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b043 Torque limit,
third quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b044 Torque limit,
fourth
quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b045 Response on
reaching the
torque limit
j 00 Not active, waits until lower limit value exceeded before
accelerating or decelerating
00
01 Active, continues to accelerate or decelerate despite
exceeded torque limit
b046 Reverse rota-
tion protection
j 00 Anticlockwise operation is allowed. 00
01 Anticlockwise operation is not allowed.
1) If SLV control is active, you should set the pulse frequency to at least 2.1 kHz with PNU b083 (a Section Pulse frequency, Page 164).
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616