Programming the control
signal terminals
01/02 AWB8230-1415GB
116
Digital fault message output
With this function, you can define whether the DV6 issues a 3-bit
encoded signal to digital outputs 11 to 13 or a 4-bit encoded
signal to outputs 11 to 14 when a fault message is issued.
X Under PNU C062, specify the digital fault message output.
The table below shows all digital fault messages.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C062 Digital fault
message
– j 00 No output to the digital outputs 00
01 3-bit encoded output to digital outputs 11 to 13
02 4-bit encoded output to digital outputs 11 to 14
Digital output 4-bit encoded 3-bit encoded
14 13 12 11
Fault message Cause Fault message Cause
0000None – None –
0001
E01 to E04 Overcurrent E01 to E04 Overcurrent
0010E05 Overload E05 Overload
0011
E07, E15 Overvoltage E07, E15 Overvoltage
0100
E09 Undervoltage E09 Undervoltage
0101
E16 Intermittent mains failure E16 Intermittent mains failure
0110
E30 IGBT fault E30 IGBT fault
0111
E06 Braking device overload – –
1000
E08, E11, E23 • EEPROM fault
• CPU fault
• GA fault
– –
1001
E10 Fault in current transformer – –
1010E12, E13, E35, E36 • External fault message
• Unattended start protection
triggered
• Thermistor fault
• External brake fault
– –
1011
E14 Earth fault – –
1100– – – –
1101
E21 Overtemperature in power section – –
1110
E24 Mains phase failure – –
1111
E50 to E79 • RS 485 fault
• Slot 1 or 2 fault
• Fault 0 to 9
– –