Setting Parameters
01/02 AWB8230-1415GB
128
SLV and 0 Hz SLV control
With SLV and 0 Hz SLV control, you can achieve a high torque
output and speed stability. For a detailed description of SLV
control, a Section SLV and autotuning, Page 171.
Vector control with optional DE6-IOM-ENC module
If you are using a DE6-IOM-ENC feedback (encoder) module and
want to use it to regulate the motor torque, set PNU A044 to 05.
For a detailed description of, see manual AWB8240-1416... for the
encoder module.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A044
A244
A344
Voltage/
frequency
characteristic
00 Linear V/f characteristic (constant torque). 00
01 Quadratic V/f characteristic (reduced torque)
02 User-definable
03 Sensorless vector control (SLV)
1)
is active
04 0 Hz SLV
1)
is active
05 Vector control
1)
with optional DE6-IOM-ENC module
A045 Output voltage
j j 20 to 100 %
of the input
voltage
The output voltage
can be set from 20
to 100 % of the
input voltage.
100
b100 Frequency
coordinate f
1
0 to 400 Hz First frequency coordinate of the V/f characteristic
3)
0
b101 Voltage coordi-
nate V
1o
0 to V
1
2)
or
PNU A082
First voltage coordinate of the V/f characteristic
3)
0.0
b102 Frequency
coordinate f
2
0 to 400 Hz Second frequency coordinate of the V/f characteristic
3)
0
b103 Voltage coordi-
nate V
2o
0 to V
1
2)
or
PNU A082
Second voltage coordinate of the V/f characteristic
3)
0.0
b104 Frequency
coordinate f
3
0 to 400 Hz Third frequency coordinate of the V/f characteristic
3)
0
b105 Voltage coordi-
nate V
3o
0 to V
1
2)
or
PNU A082
Third voltage coordinate of the V/f characteristic
3)
0.0
b106 Frequency
coordinate f
4
0 to 400 Hz Fourth frequency coordinate of the V/f characteristic
3)
0
b107 Voltage coordi-
nate V
4o
0 to V
1
2)
or
PNU A082
Fourth voltage coordinate of the V/f characteristic
3)
0.0
b108 Frequency
coordinate f
5
0 to 400 Hz Fifth frequency coordinate of the V/f characteristic
3)
0
b109 Voltage coordi-
nate V
5o
0 to V
1
2)
or
PNU A082
Fifth voltage coordinate of the V/f characteristic
3)
0.0
b110 Frequency
coordinate f
6
0 to 400 Hz Sixth frequency coordinate of the V/f characteristic
3)
0
b111 Voltage coordi-
nate V
6o
0 to V
1
2)
or
PNU A082
Sixth voltage coordinate of the V/f characteristic
3)
0.0
b112 Frequency
coordinate f
7
0 to 400 Hz Sevenths frequency coordinate of the V/f characteristic
3)
0
0
100
50
[%]
U
f