01/02 AWB8230-1415GB
Electrical connection
39
Function of the control signal terminals
Table 6: Meaning of the control signal terminals
No. Function
Level WE Technical data, description
Supply voltages
h Setpoint voltage output +10 V H Supply voltage for external setpoint potentiometer.
Load carrying capacity: 20 mA
Reference potential: Terminal L
P24 Control voltage output
+24 V H Supply voltage for actuation of digital inputs 1 to 8
and FW.
Load carrying capacity: 100 mA
Reference potential: Terminal CM1
Reference potentials
CM1 Reference potential 0 V Reference potential terminals 1 to 8, FM, FW,
TH and P24
CM2 External control voltage
input
Up to 27 V Connection: reference potential (0 V) of the external
voltage source for the transistor outputs, terminals
11 to 15.
Load carrying capacity: Up to 250 mA
(sum of terminals 11 to 15)
L Reference potential
0 V Reference potential, terminals AM, AMI, H, O,
OI and O2
PLC Common connection,
terminals 1 to 8 and FW
By default, the frequency inverters are supplied with a link between PLC and CM1, so that the potential on terminal
PLC and therefore on the digital inputs that are not energized is 0 V (negative logic). If PLC is applied to P24,
the control logic is positive.
Digital inputs
1 Digital input HIGH = +12 to +27 V
LOW = 0 to +3 V
RST = reset PNP logic, configurable, R
i
= 4.7 kO Reference
potential: Terminal CM1
2
AT = analog input changeover
3
JOG = jog mode
4
FRS = controller inhibit
5
2CH = second parameter set
6 FF2 = fixed frequency 2
7
FF1 = fixed frequency 1
8
REV = anticlockwise operation
FW Digital input, clockwise
operation
R
i
= 4.7 kO Reference potential: Terminal CM1
Analog inputs
O Analog input 0 to +10 V H Frequency setpoint value
(0 to 50 Hz)
R
i
= 10 kO
Reference potential: Terminal L
OI Analog input
4 to 20 mA Frequency setpoint value
(0 to 50 Hz)
R
B
= 250 O
Reference potential: Terminal L
O2 Analog input frequency
setpoint
10 V to +10 V H Resolution: 12 bit
Input impedance: 10 kO
Reference potential: Terminal L
TH Thermistor input
Minimum thermistor rating: 100 mW
Reference potential: Terminal CM1