01/02 AWB8230-1415GB
Signalling relay terminals K11,
K12, K14
117
Signalling relay terminals K11, K12, K14
If a fault occurs, the signalling relay (changeover) is triggered. The
switching conditions can be programmed as required.
By default, the signalling relay output is used for signalling faults,
but you can also use it as a normal programmable digital output.
To do this, enter a suitable value under PNU C026 (default
value: 05, output used for signalling faults).
Table 20: Default setting of the signalling relay
X Under PNU C026, enter the type of signalling.
X Use the above table to configure contact K11-K12 or K11-K14
as make or break contacts under PNU C036.
Default setting of the signalling relay Reconfigured signalling relay terminals (PNU C036 = 00)
Fault or DV6 switched off Run signal Fault message Run signal or DV6 switched off
Voltage Operating
state
K11-K12 K11-K14 Voltage Operating
state
K11-K12 K11-K14
On Normal Open Closed On Normal Closed Open
On Fault Closed Open On Fault Open Closed
Off – Closed Open Off – Closed Open
K12K11 K14
K12K11 K14 K12K11 K14
K12K11 K14