Setting Parameters
01/02 AWB8230-1415GB
164
Parameters U001 to U012, PNU b037 = 02
In parameter group U, you can save any twelve parameters
a Section User-defined parameters parameter group U,
Page 176), When you set PNU b037 to 02, only these and
PNU b037 are shown.
Pulse frequency
High pulse frequencies result in less motor noise and lower power
losses in the motor but a higher dissipation in the power amplifiers
and more noise in the mains and motor cables. You should there-
fore set the pulse frequency as low as possible.
During DC braking, the pulse frequency is automatically reduced
to 1 kHz.
b098 01, 02 b099, C085 Thermistor function
b050 01
b051 to b054 Behaviour on power failure
b120 01
b121 to b126 Brake control
C021 to C025, C026 02, 06
C042, C043 Frequency reached signal
03 C040, C041 Overcurrent signal
07
C055 to C058 Overload
21
C063 0 Hz signal
24, 25
C045, C046 Frequency reached signal
26
C111 Overload signal 2
PNU Value
PNUs which are hidden when PNU b037 is
set to 01
Function
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b037 Display mode j 00 All parameters are shown. 00
01 Only relevant parameters are shown.
02 Only PNU b037 and the parameters entered in PNU U001 to
U012 are shown.
PNU Name Adjustable in RUN
mode
Value WE
Normal Extended
b083 Pulse
frequency
0.5 to
15 kHz
5
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616