EasyManua.ls Logo

Moeller DV6-340 Series - Heavy mains starting (CS)

Moeller DV6-340 Series
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01/02 AWB8230-1415GB
Programmable digital inputs
1to8
91
Heavy mains starting (CS)
The CS function is used for starting drives with an extremely high
starting torque directly from the mains. This means that a smaller,
less expensive frequency inverter can be used, since the DV6 has
to deliver only the motor full load current, not the high starting
current (for example 50 A starting current, 15 A motor full load
current).
To use this function, the system must be wired as shown in
Figure 81.
Figure 81: DV6 series frequency inverters with K2M bypass contactor, K3M motor contactor and K1M mains contactor
F11: 6 A miniature circuit-breaker, for example FAZ-B6
L1 L2 L3
L1
L2
L3
PE
K1M
K2M
Q1
L1 L2 L3
L3L2L1
531
531
L1
Z1
Z2
PE
PE
U
V
W
PE
TH
CM1
M1
K3M
DF6-340-...
DV6-340-...
III
Q11
III
e
K11
F11
P24 FW
FWD
CS
2PER0 T0
M 3 h
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616