b024 Current limit
characteristic 2
– j 00 Motor current limit not active 01
01 Motor current limitation active in all operating states
02 Motor current limitation not active during acceleration
03 Motor current limitation active in every operating state. If
the motor current limit is reached in regenerative mode, the
frequency is increased until the current has fallen below the
set motor current limit.
04 Motor current limitation to achieve higher starting currents
not active in the acceleration phase. If the motor current
limit is reached in regenerative mode, the frequency is
increased until the current has fallen below the set motor
current limit.
b025 Tripping
current 2
– j 0.5 to 2 x I
e
Setting range of the tripping current as a multiple of the
frequency inverter rated current, i.e. the range is given in
amperes (A).
1.5x
I
e
1)
b026 Time constant 2 – j 0.1 to 30 s When specified current limit is reached, the frequency is
reduced in the time set here.
Caution: If possible, do not enter a value below 0.3 here!
1.0
1) Inverter rated current
PNU Name
Adjustable in RUN mode Value Function WE
Normal Extended