01/02 AWB8230-1415GB
Overview
57
FA4 24 Frequency exceeded (2) The FA4 signal is output when the frequency rises above the value
under PNU C045 or falls below the value under PNU C046.
FA5 25 Frequency reached (2) The FA5 signal is output when the frequency set under PNU C045 or
C046 is reached (hysteresis).
OL2 26 Overload alarm 2 The OL2 signal is output when the motor current exceeds the value
set under PNU C111.
CM2 – 0V 0 V reference potential for programmable digital outputs 11 to 15.
These are open collector outputs and are controlled through opto-
couplers. CM2 is isolated from reference potential L.
Signalling relay
2)
K11 – Signalling relay contacts During normal fault-free operation, terminals K11-K14 are closed. If a malfunction occurs or the
supply voltage is switched off, the terminals K11-K12 are closed.
Maximum permissible values:
• 250 V ~; maximum load 2.5 A (purely resistive) or 0.2 A (with a power factor of 0.4)
• 30 V H; maximum load 3.0 A (purely resistive) or 0.7 A (with a power factor of 0.4)
• Minimum required values: 100 V ~ at a load of 10 mA or 5 VH at a load of 100 mA
K12
K14
1) To activate the function, enter this value in the corresponding parameter.
2) This output can be used as both a signal output and a normal digital output.
Name Value
1)
Function Description