Programming the control
signal terminals
01/02 AWB8230-1415GB
56
Programmable digital outputs 11 to 15
RUN 00 RUN signal The RUN signal is output during operation of the motor. Connection of a signal
relay to a digital output
11 to 15:
Transistor output
(open collector)
(maximum 27 VH, 50 mA)
FA1 01 Signal when frequency is
reached
f
s
= setpoint frequency
FA2 02 Signal when frequency is
exceeded (1)
If a digital output is configured as FA1, a signal is issued as long as
the setpoint value is reached. If a digital signal is configured as FA2,
a signal is output as long as the frequencies defined under PNU C042
and PNU C043 are exceeded.
OL 03 Signal on overload
The OL signal is output when the overload alarm threshold (adjus-
table under PNU C041) is exceeded.
OD 04 Signal on PID control
deviation
The OD signal is output when the PID control deviation set under
PNU C044 is exceeded.
AL 05 Signal (alarm) on fault
The AL signal is issued when a fault occurs.
FA3 06 Frequency reached (1)
The FA3 signal is issued when the output frequency lies in the
frequency range defined under PNU C042 and C043 (plus tolerance).
OTQ 7 Torque reached
(exceeded)
The OTQ signal is output when the set torque is reached or exceed.
IP 8 Mains failure, immediate
stop
The IP signal is issued on intermittent mains failure.
UV 9 Undervoltage signal The UV signal is output on undervoltage.
TRQ 10 Torque limitation The TRQ signal is output when the torque limits set under PNU b041
to b044 are reached.
RNT 11 Running time exceeded The RNT signal is output when the running time set under PNU b034
is exceeded.
ONT 12 Mains On time exceeded The ONT signal is output when the running time set under PNU b034
is exceeded.
THM 13 Motor thermal overload The THM signal is output when the motor overload warning thres-
hold set under PNU C061 is exceeded.
BRK 19 Enable signal for
external brake
The BRK signal is output to enable an external brake; adjustable
under PNU b120 to b126.
BER 20 Brake fault The BER signal is output when the BOK input of the external brake is
not deactivated; adjustable under PNU b120 to b126.
ZS 21 Zero speed The ZS signal is output when the motor is at rest (zero speed).
DSE 22 Speed deviation
exceeded
The DSE signal is output when the deviation of the actual speed from
the setpoint value is greater than specified under PNU P027 (only
with optional DE6-IOM-ENC module).
POK 23 Positioning The POK signal is output when positioning has been completed (only
with optional DE6-IOM-ENC module).
Name Value
1)
Function Description
24 V
50 mA
12CM2
FA1
f
s
FA2
f
2
f
1