Programming the control
signal terminals
01/02 AWB8230-1415GB
112
b041 Torque limit,
first quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b042 Torque limit,
second
quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b043 Torque limit,
third quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
b044 Torque limit,
fourth
quadrant
j 0 to 200 % For DV6-340-075 to DV6-340-45K 150
0 to 180 % For DV6-340-55k to DV6-340-132K
no For all variables: function not active.
1) If SLV control is active, you should set the pulse frequency to at least 2.1 kHz with PNU b83 (a Section Pulse frequency, Page 164).
PNU Name
Adjustable in RUN mode Value Function WE
Normal Extended