01/02 AWB8230-1415GB
Controlled deceleration
161
If the mains power fails during controlled deceleration
(PNU b050 = 01), deceleration starts as soon as the internal DC
link voltage V
DC
falls below the threshold set under PNU b051.
To ensure that the control electronics are supplied with power, the
current output frequency f
O
is reduced by the frequency jump set
under PNU b054. The motor then runs in regenerative mode and
feeds the internal DC link voltage V
DC
. Deceleration now takes
place after the set deceleration ramp (PNU b053). If, due to a high
mass inertia, the internal DC link voltage V
DC
becomes excessi-
vely high, the deceleration ramp is interrupted until the voltage
falls below the threshold defined under PNU b052.
Figure 166: Function chart for controlled deceleration
V
DC
:Internal DC link voltage
V
UV
:Voltage threshold for the control electronics
f
O
: Output frequency
U
UV
PNU b052
PNU b051
PNU b054
PNU b053
PNU b053
U
DC
f
O
t
t
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b050 Controlled
deceleration
00 Controlled deceleration is not active. 00
01 Controlled deceleration is active.
b051 Starting
voltage for
deceleration
0 to 1000 V When the internal DC link voltage falls below this value,
controlled deceleration starts
0.0
b052 Voltage for
ramp stop
0 to 1000 V When the internal DC link voltage rises again, the decelera-
tion ramp PNU b053 is interrupted.
0.0
b053 Deceleration
time
0.01 to 3600 s During this time, the motor is decelerated. 1.00
b054 Frequency
jump
0.00 to
10.00 Hz
The frequency inverter reduces the output voltage by this
value so that the motor works in regenerative mode.
0.00